• Software en engineering in-house
  • Retourneren eenvoudig via selfservice
  • Technische support en engineering beschikbaar
X20 Analog 3xI 480VAC, 4xI 1A, CT ground
I/O SystemsX20
X20AP3122

X20 Analog 3xI 480VAC, 4xI 1A, CT ground

📦2-3 weken

Quantity

4 AC inputs

Resolution

10 mV, with voltage connected directly

ATEX

Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X

Measurement Category

CAT II

Vertical Mounting Orientation

-25 to 50°C

Bus / I/O Power Supply - Ground

Tested at 510 VAC, 1 min

€ 339,26excl. BTWincl. BTW € 410,50

Zakelijk klant? Vraag een offerte aan of log in voor uw prijs.

Omschrijving

  • Calculates RMS values from currents and voltages
  • Calculates active, reactive and apparent power
  • Phasing detection
  • Measures individual phases and calculates cumulative values
  • Optional measurement of current through the neutral conductor
  • Calculates frequency and harmonics with high precision
  • Time timestamp: Moment when measured value groups are read Power monitoring
  • These modules measure active, reactive and apparent power individually for each of the 3 phases a
  • Calculates RMS values from currents and voltages
  • Calculates active, reactive and apparent power
  • Phasing detection
  • Measures individual phases and calculates cumulative values
  • Optional measurement of current through the neutral conductor
  • Calculates frequency and harmonics with high precision
  • Time timestamp: Moment when measured value groups are read Power monitoring
  • These modules measure active, reactive and apparent power individually for each of the 3 phases as well as all of them collectively. The power consumption of each phase is also recorded individually and in total. In addition, the modules provide the RMS values for voltage and current on the 3 phases. When measuring the current, the value of the current through the neutral conductor can also be detected and monitored. Measurement of the mains frequency and the phase angle of the 3 phases (current and voltage) complete the power measurement data.Energy management
  • The integrated functions on the modules map the immediate power requirements of the machine in detail as well as record its total power consumption. For the user, all relevant data is prepared and made available in the process image.The ability to measure currents and voltages up to the 31st harmonic enables higher precision recording of RMS values than is generally possible. This allows the modules to easily cope with irregular sine curves and makes them well-suited to renewable energy applications. In these types of applications, for example, being able to accurately measure the frequency at a resolution of 0.01 Hz between 45 and 65 Hz is a great advantage. In general, the modules are suitable for use with 1-phase, 2-phase or 3-phase networks.Net
  • Time timestamp of readout moments
  • For many applications, not only the measured value is important, but also the exact moment when a group of measured values is read out. The module is equipped with a Net
  • Time timestamp function for this that supplies a timestamp for the recorded position and trigger time with microsecond accuracy.The timestamp function is based on synchronized timers. If a timestamp event occurs, the module immediately saves the current Net
  • Time. After the respective data is transferred to the CPU, including this precise moment, the CPU can then evaluate the data using its own Net
  • Time (or system time), if necessary.

Productinformatie

Serie
X20
Land van herkomst
AT

Gerelateerde producten